Stepped Fault Line Selection Method Based on Spectral Kurtosis and Relative Energy Entropy of Small Current to Ground System

Table 9

SK relative energy entropy with different intensity noise ( , ).

SNR/dBFault lineSK relative energy entropy Entropy multiple Results
S1 S2 S3 S4

−1.5678Overhead line S13.06651.27111.35202.70912.41 > 2S1
Cable line S40.98980.80894.53475.69221.22 < 2S4

−5.5678Overhead line S12.90611.17251.81922.73492.48 > 2S1
Cable line S40.93750.53883.75735.28261.74 < 2S4

−10.5678Overhead line S12.84491.03591.76982.40712.75 > 2S1
Cable line S40.82670.44813.45863.96731.84 < 2S4

−13.5678Overhead line S12.68140.69512.03112.15383.86 > 2S1
Cable line S41.19790.76464.57265.85591.57 < 2S4