Research Article

Foulant Characteristics Comparison in Recycling Cooling Water System Makeup by Municipal Reclaimed Water and Surface Water in Power Plant

Table 2

Comparison of water quality of municipal reclaimed water and surface water.

NumberIndexUnitMunicipal reclaimed waterSurface water

1TurbidityNTU1.2~4.31.9~5.7
2pH7.22~7.917.05~8.57
3Conductivityμs/cm930~1101566~753
4TDSmg/mL540~587283~356
5Clmg/L109.53~125.2926.30~48.45
6mg/L100.15~122.2584.76~103.29
7Total alkalinity (CaCO3)mg/L138.57~143.24150.25~168.78
8Total hardness (CaCO3)mg/L286.36~296.56268.77
9Calcium hardness (CaCO3)mg/L176.5122.8
10mmol/L3.4643.572
11mg/L4.2~6.82.24~3.5
12TPmg/L0.21~0.390.13~0.17
13Soluble TPmg/L0.15~0.210.10~0.15
14Orthophosphatemg/L0.12~0.170.06~0.09
15TNmg/L35.223.26
16Total Femg/L0.0750.061
17Almg/L<0.04<0.04
18Znmg/L<0.0180.12
19Cumg/L<0.010<0.010
20Mnmg/L<0.0010.005
21Simg/L4.361.5
22Surfactantmg/L0.14<0.05
23Total bacterial countcfu/mL(1.5~4.9) × 1041.0 × 103