Abstract

Aiming at the demand for medium- and high-voltage port access capability in energy router, this study proposes a quad-port DC/DC converter topology scheme based on modular multilevel converter (QP-M2DC). Compared with the traditional multiterminal energy routing converter, it has the advantages of high modularity, strong flexibility, and high power density. In addition, for the modular structure on the medium- and high-voltage sides, this study proposes a narrow phase-shift cyclic modulation strategy, which reduces the system need for voltage balance control and simplifies the overall system control. This study comprehensively introduces and analyses the QP-M2DC topology, working principle, high-frequency link equivalent, and power characteristics, then establishes an equivalent model of system control, and proposes a control scheme for a multiterminal energy routing converter. Finally, a simulation model of the system is established through PLECS, and the simulation results show that in such a narrow phase-shift modulation strategy, the proposed topology can have stable operation in a variety of patterns, reduce the capacitance, and achieve better voltage balance at the same time. The experimental results show the converter efficiency of up to 97.8%. It further shows the superiority of the proposed topology structure and the correctness and effectiveness of the proposed control schemes.

1. Introduction

With the development of microgrid technology, medium- and high-voltage DC microgrid (DCMG) has become the main research hotspots now. Among them, the medium- and high-voltage DC distribution system is a key link in the establishment of modern DCMG. The distributed power sources in the microgrids include photovoltaics, wind turbines, fuel cells, and energy storage units, and the loads also include a variety of DC loads and AC loads [1]. Due to the diversification of its usage scenarios, multi-bus power distribution structure is required, and its interface types can be a variety of distributed energy sources, energy storage systems, AC and DC loads, etc. [2]. Therefore, in the DCMG energy management system, as an important part of the electrical energy router, it can control the bidirectional flow of energy and realize the voltage conversion and electrical isolation between the medium-voltage direct current (MVDC) and the low-voltage direct current (LVDC). The core device for plug and play is the DC transformer (DCT).

The energy scheduling in DCMG requires multidirectional electric energy routing equipment. To ensure the bus voltage stability and continuous operation of DCMG, it is necessary to configure appropriate energy storage units and bidirectional converters. When excess power is generated inside the microgrid, the extra energy is fed back to the grid, and more energy is obtained from the grid when needed. This requires the design of multiterminal energy routing devices in the DCMG distribution system. Therefore, to facilitate the connection of multiple new energy sources and energy exchange between power grids, multi-port energy routing schemes based on different usage scenarios have been proposed [38]. Reference [3] introduced an energy routing topology for wind storage grid-connected system, using a full-bridge power converter to implement an independent hybrid renewable energy DC grid system with battery storage. Two different converter structures were proposed in [4, 5] for household energy routing equipment, including residential microgrid topology consisting of photovoltaic and fuel cell multi-port DC/DC converters and single-phase grid-connected bidirectional inverters, and the topology using a multi-winding high-frequency transformer to connect each H-bridge port for isolation and power redistribution. Liu et al. [6] proposed a solid-state transformer topology based on quad-active bridge (QAB), including the power transmission analysis, modelling, and control strategy of QAB and presented a new equivalent model of multi-winding transformer. Frutos et al. [7] designed a linear quadratic regulator controller for a quad-port converter based on the average equivalent model of QAB, and the control strategy can resist step disturbance. The abovementioned topology structure can realize the energy routing function through a reasonable control scheme, but it does not have the medium- and high-voltage access capability.

The dual active bridge (DAB) serves as a basic dc transformer, and it is generally regarded as the core circuit of the next generation of high-density power conversion systems [8]. However, due to the power capacity limitations of power electronic switches, an independent DAB unit cannot be used as a permanent DCT between the MVDC bus and the LVDC bus of the DCMG. Therefore, to improve the power capacity and voltage level of DCT, the structure of input series and output parallel based on DAB is a common scheme for DCT to connect MVDC and LVDC [9]. However, this topology also has reliability problems. When a fault occurs, the DC capacitor of the DAB should be recharged after the fault is eliminated, which will slow down the recovery process of current fault. In addition, the existence of DC capacitors in the system makes it difficult to implement the redundancy scheme. When a submodule (SM) fails, the DCT must stop working, which will reduce the reliability of the system. Therefore, in the study of the DC/DC conversion topology scheme with the introduction of medium- and high-voltage ports, the DC converter based on the modular multilevel converter (MMC) structure has also begun to attract the attention of some scholars. Li et al. [10] made a systematic comparison between multilevel high-frequency link dc transformer (abbreviated MDCT) based on modular multilevel converter and multilevel dc link dc transformer (abbreviated ADCT) based on DAB for MVDC application. MDCT uses MMC structure to increase the voltage level, compared with ADCT still using DAB structure as the basic unit, although MDCT requires more switches and high-frequency inductance on the high-voltage side of the same voltage level, it can reduce the number of high-frequency transformers. In addition, the number of H-bridges on the LVDC side of MDCT is only determined by the power level, which can be less than the number of SMs on the MVDC side. However, the ADCT has poor flexibility because the number of modules on the low-voltage side is exactly the same as that on the medium-voltage side [1113] provided a phase-shift modulation strategy for MMC-based dc converters, but this modulation strategy will cause imbalance of SM voltage, which requires the additional introduction of voltage balance control strategy. Shao et al. [14] proposed a capacitor voltage balance control strategy that does not rely on arm current detection by introducing a small delay time into the switch pulse of SMs. Sun et al. [15] proposed an optimized dual-phase-shift voltage balance control strategy and adopted NLM algorithm for the high-frequency switch controlled by voltage balance.

Therefore, the topology of the multi-port energy routing scheme for most current uses is the full-bridge structure. It uses multi-winding transformer to integrate multiple full-bridge structure, but there is current recovery after the failure recovery is slow and redundancy scheme is difficult to realize. The modular structure of multilevel converter has the advantage of flexibility [1623]. In this study, a four-port converter is constructed. The control mode of multi-port converter is mainly based on phase-shift control, and the voltage balance control strategy is introduced to solve the voltage imbalance caused by phase-shift control or optimize the phase-shift control and put forward a kind of double-phase-shift voltage balance control strategy. This study puts forward a kind of narrow phase-shift modulation strategy and reduces the influence of the voltage unbalance of converter.

Based on the above analysis, this study proposes a topology scheme of quad-port DC/DC converter based on modular multilevel structure to realize the multiterminal power routing transformation with medium- and high-voltage port access in the DCMG multi-bus distribution application. This topology integrates the advantages of MMC and traditional DAB, with a high-voltage working level and flexible modular design. In addition, when the MMC structure on the medium-voltage side works in high-frequency quasi-square-wave modulation, the SM can meet the requirements using thin-film capacitance with a small capacitance value, which improves the power density of the system. Compared with the traditional multi-port energy routing schemes, higher reliability exists in the proposed converter. It not only meets the needs of high power capacity but also uses the film instead of electrolytic capacitors. The converter has small internal energy and high power density. The proposed narrow phase-shift cyclic modulation strategy avoids the problem of voltage unbalance control strategy in traditional phase-shift-down control scheme and simplifies the control.

In this study, the topological structure, working principle, equivalent analysis of high-frequency link (HFL), and power transfer characteristics of QP-M2DC are comprehensively introduced and analysed, the equivalent model of system control is established, and a control scheme of multiterminal energy routing converter is proposed. In addition, a kind of MMC side narrow phase-shift cyclic modulation strategy is proposed, which reduces the need for equilibrium control and simplifies the overall control of the system. Finally, the simulation model of QP-M2DC is established, and the simulation results verify the correctness and effectiveness of the proposed scheme. At the same time, an experimental platform is set up, and the maximum efficiency of the proposed scheme can reach 97.8%, which further verifies the superiority of the scheme.

2. Operating Characteristics of Proposed QP-M2DC

2.1. QP-M2DC Topology

The QP-M2DC topology proposed in this study is shown in Figure 1 The QP-M2DC topology consists of an MVDC port transform module, quad-port high-frequency link, and three LVDC port transform modules. The MVDC interface of the topology is composed of modular multilevel structure. Each phase of the bridge arm is composed of a semibridge SMi and a bridge arm inductor in series, and each semibridge module contains an SM capacitance. The voltage balance of SMs is the prerequisite for the MMC to modulate the ideal voltage, and it is also the key to the stable operation of the system. The HFL consists of a multi-port high-frequency transformer and a power inductor to transfer energy. The LVDC port consists of an H-bridge, and the energy storage port includes a half-bridge buck/boost, which ensures bidirectional transmission of energy at the low-voltage port.

Compared with the traditional multilevel DAB cascade structure, the proposed QP-M2DC topology scheme adopts MMC structure to realize the connection function of medium and high voltage, which meets the demand of high power capacity. Compared with DAB cascade structure, the proposed topology uses thin-film capacitor with small capacitance value to replace electrolytic capacitance, which has the advantage of small internal energy storage in the converter. In the application of DCMG power distribution in low and medium power levels, traditional DAB cascade structure to meet the voltage level of medium- and high-voltage ports, the traditional DAB cascade structure has the same number of transformers as that of medium- and high-voltage sides, which is not conducive to the design of power density improvement of the system. The topology of the MMC in this study is based on voltage level as standard for MMC on the high-voltage side and current level as standard on multilevel power module on the low-voltage side. There is no mutual restriction on the number of modules in the two-stage design. It has more flexibility, which also contributes to the improvement of system power density.

In Figure 1, Va and Ia, respectively, represent the voltage and current of the high-voltage side. Vb, Vc, Vd, ib, ic, and id, respectively, represent the output voltage and current of the three ports on the low-voltage side. Vaj and iaj are the voltage and current of MMC bridge arm. La, Lb, Lc, and Ld are HFL phase-shift inductors. An equivalent analysis of high-frequency link phase-shift inductor will be carried out later.

2.2. MMC Modulation Strategy

The topology is divided into MVDC side and LVDC side, and the MVDC side is composed of MMC structure. There are many modulation strategies for the MMC. Reference [24] adopted a carrier phase-shift control (CPS-PWM), as shown in Figure 2(a), and the control signals of the upper and lower bridge arms are obtained by comparing N carrier waves with a phase difference of 2π/N with modulated waves of opposite phase. This modulation strategy cannot guarantee the natural balance of the voltage of the SMs in QP-M2DC, and it is difficult to ensure that N SMs are put in each phase at any time after the addition of the balancing strategy, so a large bridge arm buffer inductance is often needed to help suppress loop current between phases. He et al. [25] introduced a carrier stack modulation (CAM-PWM). As shown in Figure 2(b), by superimposing the carrier waves and comparing with the modulated wave, the number of carrier waves that are smaller than the modulated wave is the number of SMs of the upper (or lower) bridge arm, and the output voltages of the modules are superimposed to obtain the output voltage waveform of the upper (or lower) bridge arm. In high-frequency isolated DC/DC transformation, both CPS-PWM and CAM-PWM modulation strategies need high-frequency modulation waves to realize, so the carrier frequency will be higher, which means MMC will work at very high switching frequency, which is difficult to achieve in practical engineering.

Based on the shortcomings of the traditional modulation strategy analysed above in the high-frequency application of MMC, this study proposes a narrow phase-shift cyclic (NPSC) modulation scheme. A small phase-shift angle θ is given between the control signals of adjacent SMs in the MMC bridge arm. When θ is small, the MMC bridge arm voltage is a stepped wave similar to the square wave, which can not only achieve the higher voltage level requirements but can also avoid damage to the circuit due to excessive .

Although the control strategy of Figure 3(a) can achieve the requirements of the bridge arm high-voltage level, the fixed difference in the charging and discharging timing of the bridge arm SMs will cause the voltage imbalance. Therefore, on this basis, a NPSC modulation strategy is designed as shown in Figure 3(b), the phase-shift angle of n SMs is set as θ, 2θ, …, in the first cycle of drive control, and the second cycle changes the phase-shift angle to , …, 2θ, θ. The NPSC modulation can realize the charging and discharging balance of the capacitances, and the voltage balance of the SM can be realized under the ideal parameter condition of MMC, which reduces the demand of MMC for the SM voltage balance control.

2.3. Phase-Shift Principle

Combined with the HFL design in Figure 1, similar to the analysis of DAB in power transmission control, each port of the HFL is equivalent to a voltage source, as shown in Figure 4. The flow direction and magnitude of power transmitted between the ports are controlled by the phase-shift angle between the voltage sources. When energy is transferred between the low-voltage ports, the transfer method can be equivalent to a DAB structure, the voltage of each transformer port is a square wave, and the power is transferred through the phase-shift angle between the low-voltage ports, as shown in Figure 5(a). The power transfer formula can be referred to DAB, and the traditional DAB power transfer formula can be easily obtained [18] as follows:where φ is the phase-shift angle between the primary and secondary sides.

When the energy is transferred from the high-voltage side to the low-voltage side, since the high-voltage side MMC structure adopts the NPSC modulation strategy proposed in this study, compared with the traditional DAB structure, a stepped quasi-square wave will be generated on the primary side of the transformer. For the controllable transmission of power between multiple ports, it is necessary to study the applicability of phase-shift control in QP-M2DC topology. For example, the energy transfer from high-voltage port to any other port is taken, and the waveforms of the inductor current iL and the voltage source are shown in Figure 5(b).

The expression of the MVDC port participating in the power transfer under the NPSC modulation strategy is now derived according to (1). The research scheme considers the situation when φ > (N − 1) θ/2, and the formula of inductive current is derived as follows:

To simplify the analysis, φ1 = φ − (N − 1) θ/2 is taken, where V1 is the voltage amplitude, n is the transformer ratio, L is the phase-shifted inductance converted to the primary side, ω = 2πf, and m is the number of steps. From iL (0) = − iL (π), we have the following:

Thus, the expression of MVDC port participating in power transfer under the NPSC modulation strategy can be obtained as follows:

3. Multiport Energy Transfer Analysis

3.1. HFL Equivalent Analysis

The MVDC is equivalent to port a, and the power transfer between any two ports is mainly accomplished through the phase-shift control of quasi-square-wave voltage. Due to the particularity of the structure of port a, the energy transmission is temporarily defined as the transfer of port a to other ports in the HFL equivalent analysis. As shown in Figure 5(b), the square-wave voltage generated by port a is set to Va, the current is ia, and the inductance is La. This study does not consider the effect of high-frequency transformer internal leakage inductance. The modulated voltage, current, and inductance at port k (k = b, c, d) are equivalent to port a as follows:

Port a is selected as the sending port, while port k (b, c, and d) is selected as the receiving ports. According to the equivalent circuit in Figure 4, the total equivalent inductance can be calculated as follows:

Similarly, the Thevenin equivalent ac voltage VThk associated with port k is defined in port a as follows:

The above is the general equation of the topology with n ports on the low-voltage side. The equivalent circuit can be obtained by combining (6) and (7).

From (4), the power transferred from port a to port k can be obtained as (8), where φak is the phase-shift angle between port a and port k:

According to Figure 6, the link inductance between the ports can be expressed as follows:

For the average model of this topology, the periodic average current value of the ripple current ia on the DC side of port a is defined as Ia. The average current generated by port k, defined as Iak, is given by the following equation:

When , equations (6)–(9) are substituted into (10), and we get the following equation:

The relevant gain parameter can be calculated as follows:

Therefore, according to the superposition theorem, Ia can be expressed as follows:

According to the above analysis, the equivalent average model of QP-M2DC topology can be obtained, as shown in Figure 7.

3.2. QP-M2DC Power Characteristic

To design the rated power of the four ports, the power transfer analysis of the quad-port converter should be carried out based on each possible operating condition. Assuming that in a certain operating condition, there is a port in QP-M2DC operating at the maximum power within the allowable range of phase-shift angle, the rated power of the converter port is limited by the maximum input or output power. Therefore, the rated power of the ports in the quad-port converter depends on the number of sources and loads, as well as the direction of port power flow. The nonlinear relationship is now defined as follows:

An ideal working mode is defined; that is, each port can carry out bidirectional power transfer. Then, the maximum power transferred from port j to port k can be defined according to (8).where φ is the phase-shift angle between the two ports, θ represents the narrow phase-shift angle between the SMs, and this angle can be ignored when the source port is not an MMC structure. is the DC conversion ratio of port j and port a, and is the DC conversion ratio of port a and port k. When the djdk approximates to 1, the converter can achieve ZVS operation under light loads.

QP-M2DC can operate in DAB mode by disabling two ports. To further simplify the analysis process, the following assumptions are made: dj = 1, , and then Lak = La + Lak = 4La. The maximum power that QP-M2DC flows between any two ports is defined as , also known as the maximum link power. It can be obtained as follows:where is the maximum power that QP-M2DC can transfer when working in DAB mode. Considering the influence of θ in the control strategy, to simplify the process of power transfer analysis, it is expressed in the form of per unit value.where LDAB = 2La, when the phase-shift angle between the source and the load reaches φ, the source outputs the maximum power. In addition, in QP-M2DC, it is possible to increase the maximum transmission power between the source-load ports by enabling some of the zero-power output ports. The passive ports are hereinafter referred to as zero-power ports, as shown in Figure 8.

Figure 8 depicts the maximum power transfer state when using r sources, q loads, and zero-power ports, where α is the phase-shift angle between the zero-power ports and the source ports, and β is the phase-shift angle between the zero-power ports and the load ports. It can be concluded from Figure 8.

Assuming that there is no loss when the power is transmitted between the ports, the following can be obtained:

For the special case, when , then β = φ/2, and the maximum link power transferred from the source ports to the load ports is as follows:

Therefore, when designing the system power transfer level, after adding the zero-power port as a channel for system power transfer, the maximum unit power of each source port is as follows:

Similarly, the maximum unit power of each load port is as follows:

3.3. QP-M2DC Power Flow Analysis

According to the above analysis, the average equivalent model of QP-M2DC can be obtained, as shown in Figure 9. When reaching the maximum link power between any two ports of QP-M2DC, the power transfer of the converter depends on the number of source ports, zero-power ports, and load ports.

Figure 10 shows a schematic diagram of the converter working at maximum power, where αd can be solved by (24). When QP-M2DC works in two-port or three-port state, the zero-power ports automatically participate in the power transmission process.

The maximum link power of QP-M2DC can be obtained from (18). When working in one-source one-load (1S-1L) mode, as shown in Figure 3(a), according to (22), the available transmission power is as follows:

By the same analysis, the maximum operating power of QP-M2DC in different working modes can be obtained, as shown in Table 1.

4. Control Strategy Design

In the power scheduling process of the multi-directional energy routing converter, the characteristics of multiple types of ports need to be considered, such as the characteristics of the photovoltaic port, the multiple energy storage types, and the multi-level power supply bus port. Based on the introduction of the topology structure of QP-M2DC and the analysis of the power characteristics, this study designs a general control strategy for multi-type port power routing, as shown in Figure 11.

The overall control strategy of the energy router of the DC distribution system includes port power control of different interface types, power scheduling control, and phase-shift control strategy. The port power control uses different control strategies according to the characteristics of different devices connected, which may include power flow control of the MVDC grid, maximum power point tracking (MPPT) control of the photovoltaic module, and battery management system (BMS). The power scheduling control is based on the different functions of each port to autonomously schedule power in different applications. The phase-shift control includes the energy transfer control method between the ports and the MMC modulation strategy.

5. Simulation Results

Based on the analysis of the QP-M2DC power characteristics and the proposed system control strategy under the multimode, this study designs four typical modal simulations and defines the MVDC port as a stable medium-voltage DC bus of 20 kV constant voltage port, LVDC1 and LVDC2 ports are, respectively, 750 V and 220 V power supply double bus bars of DCMG, and the ESS port is an energy storage system port. Due to the existence of distributed energy in the DCMG, all four ports are defined as bidirectional energy transfer ports. Simulation parameters are shown in Tables 2 and 3.

In the control system, a port is set as the reference port with phase angle of 0. The voltage stability of the reference port needs to be controlled to ensure the stability of the control system, and the voltage or power of the other ports can be controlled by setting the different phase angles with the reference port after power decoupling.

According to the power characteristic analysis, it can be seen that with the increase in the number of ports, the analysis method will become more and more complex when calculating the phase-shift angles, which is difficult to achieve in practical engineering applications. Based on the above analysis, within the allowable error range, voltage, current with phase-shift angle, or power with phase-shift angle can be regarded as an approximately linear relationship. Therefore, as shown in Figure 12, a combined control scheme based on voltage, current, and power is adopted in the simulation case, and the four ports are bidirectional energy transfer ports, among which MVDC is the grid-connected port of the MVDC bus, it is the reference port of the system, and the voltage is stable, i.e., φ0 = 0.

In the simulation case, MMC modulation scheme of MVDC port adopts the NPSC modulation strategy shown in Figure 3(b). As shown in Figure 13, under this quasi-square-wave modulation strategy, when the capacitance of MMC SM is only 80 uF, the voltage fluctuation of the SM capacitor is only 0.7% and can achieve better voltage balance, which is of great significance to the stable and safe operation of the system. The function can be realized using thin-film capacitor in SM, which greatly reduces the number of electrolytic capacitors used in the system and improves the power density of the energy routing system. Figure 14 shows the modulation voltage waveform on the MMC side. The number of voltage steps is one more than the number of SM, i.e., N + 1.

Figure 15 shows the disturbance test of the QP-M2DC converter in the one-source three-load mode with the MVDC port as the source, reducing the load of the LVDC1 port by 50% at 0.5 s and reducing the load by 50% of the LVDC2 port at 0.7 s, increasing the load of ESS port from half load to full load at 0.9 s, and reducing the voltage of MVDC port by 20% at 1.1 s. From the simulation results, the port energy control strategy of QP-M2DC converter has good stability.

Figures 1618 are the HFL waveforms of the QP-M2DC converter operating in various modes. Figures 15 and 16, respectively, show the HFL waveform of one-source three-load mode when MVDC port and LVDC1 port are the sources. Figure 17 shows the HFL waveform from two-source one-load mode to three-source one-load mode. It can be seen that from simulation waveforms under various working modes the proposed energy control scheme has good performance.

6. Experimental Results

To verify the theoretical analysis, a down-scaled experimental prototype was built. Table 4 is the specific experimental parameters. dSPACE is selected as the platform controller, and the control mode is centralized control. The narrow phase-shift cyclic driving strategy, phase-shift control, and square-wave driving are realized in dSPACE, and then, the hardware dead time circuit on each submodule generates the switching signal with dead time, which is used to drive each submodule, full-bridge structure, and buck/boost structure. The four phase-shift inductors are decoupled and integrated with two groups of EE cores. The isolation four-winding transformer is wound with UU magnetic core, and the power level is designed to be 2 kW. The selection of switching devices at each port is shown in Table 5.

As shown in Figure 19, is the 750 V port voltage of QP-M2DC converter, is the 380 V port voltage, is the 220 V port voltage, and energy storage side (48 V) port voltage is . The four ports of the QP-M2DC converter are all in steady state. The voltage waveform of MVDC is in the shape of step wave with an amplitude of 768 V. The voltage waveform of LVDC1, LVDC2, and ESS is rectangular wave with a voltage amplitude of 375 V, 221.5 V, and 47.5 V, respectively. All ports work stably, which verifies the correctness of topology theory analysis.

Figure 20(a) shows the experimental waveform of QP-M2DC converter at the start stage. During the transition from the prototype device starting process to no-load operation process, the dc voltage shock of each port does not exceed 5% of the rated voltage, the input current shock is not greater than 50% of the rated value, and the starting stage works normally. Figure 20(b) shows the waveforms of each port when the 380 V port of QP-M2DC converter switches the load. The 1.6 kW load is put into the 380 V port from no load, and then, the load is removed after a period of delay. In the figure, the voltage fluctuation value of each port is less than 5.3%, and the maximum fluctuation is restored to stability after 294 ms. The port capability control strategy of QP-M2DC converter has good stability. Figure 20(c) shows the waveforms of each 220 V port in QP-M2DC converter when the load is switched off. The 120 W load is put into the 220 V port from no load, and then, the load is removed after a period of delay. In the figure, the voltage fluctuation value of each port is less than 1.9%, and the maximum fluctuation is stabilized after 97 ms. It reflects the stability of QP-M2DC converter when the 220 port is switched to load. Figure 20(d) shows the waveforms of each port in the charging process of the energy storage device of QP-M2DC converter. In the experiment, the constant current charging instruction value changes from 1 A to 3 A, and the voltage of each port runs stably. At this time, the converter works at a maximum power of 90%, and the efficiency is about 96.1%.

The efficiency of the four ports in three different working modes was tested, and the efficiency curves were drawn for three loads and one source, two loads and two sources, and one load and three sources, and results are shown in Figure 21. The full load efficiencies are 97.8%, 96.9%, and 96.1%, respectively, which proves that the proposed topology has high efficiency.

7. Conclusions

In this study, a quad-port DC/DC converter (QP-M2DC) topology scheme based on modular multilevel structure is proposed. Compared with the traditional multi-port power routing converter, this topology has advantages of high modularity, high flexibility, and high power density. Aiming at the modularization multilevel structure of medium- and high-voltage ports, this study proposes an NPSC modulation strategy, which is of great significance for the converter to reduce SM capacitance, which increases system power density and simplifies the equalization control. In this study, the topological structure, working principle, equivalent analysis of HFL, and power characteristics of QP-M2DC are comprehensively introduced and analysed, the equivalent model of system control is established, and a control scheme of multiterminal energy routing converter is proposed. A set of QP-M2DC simulation systems was built by PLECS, and the simulation results verified the superiority of the proposed topology and the correctness and effectiveness of the proposed control scheme.

The simulation results show that in such a narrow phase-shift modulation strategy, the proposed topology can have stable operation in a variety of patterns, reduce the capacitance, and achieve better voltage balance at the same time. The experimental results show the converter efficiency of up to 97.8%. It further shows the superiority of the proposed topology structure and the correctness and effectiveness of the proposed control schemes. In fact, there are some parts that need to be optimized. For example, there is room for further optimization of the design of medium-voltage high-frequency high-power transformer in the converter, including the treatment of insulation. Currently, optimization research is being carried out for this problem.

Data Availability

The data used to support the findings of this study were supplied by Jiaxun Teng under license and so cannot be made freely available. Requests for access to these data should be made to Jiaxun Teng ([email protected]).

Conflicts of Interest

The authors declare that there are no conflicts of interest regarding the publication of this study.

Acknowledgments

This work was funded by the Science and Technology Project of State Grid Corporation of China “Research funding of energy Internet multi-energy flow integration and routing technology based on multi-port energy router” under Grant PD71-19-010.