Shunt Active Power Filter Based on Proportional Integral and Multi Vector Resonant Controllers for Compensating Nonlinear Loads

Table 2

Compensation results with two control algorithms.

Order of harmonic5711131719THD (%)

Harmonic distortion before compensation (%)21.39.875.603.361.800.9226.1

Harmonic distortion after compensation (%)With PI controller2.161.861.761.801.741.827.34
With the proposed method0.720.480.350.20.180.102.86