Shunt Active Power Filter Based on Proportional Integral and Multi Vector Resonant Controllers for Compensating Nonlinear Loads
Table 2
Compensation results with two control algorithms.
| Order of harmonic | 5 | 7 | 11 | 13 | 17 | 19 | THD (%) |
| Harmonic distortion before compensation (%) | 21.3 | 9.87 | 5.60 | 3.36 | 1.80 | 0.92 | 26.1 |
| Harmonic distortion after compensation (%) | With PI controller | 2.16 | 1.86 | 1.76 | 1.80 | 1.74 | 1.82 | 7.34 | With the proposed method | 0.72 | 0.48 | 0.35 | 0.2 | 0.18 | 0.10 | 2.86 |
|
|