Research Article

Implementation of Static Line Voltage Stability Indices for Improved Static Voltage Stability Margin

Table 1

System performance of the IEEE 30-bus test system.

ā€‰Objective functions
Case 1Case 2Case 3Case 4

Pg (MW)292.83290.34289.87288.12
Qg (MVar)87.4683.3382.6360.81
Loss (MW)9.42906.94086.47134.7236
Cost ($/h)802.21829.11831.09971.55
Maximum FVSI0.24710.07220.06720.4212
Maximum Lmn0.24830.07230.06720.4221
Maximum LVSI0.90190.84390.86310.7219
Sum FVSI1.45190.63210.62732.4624
Sum Lmn1.46940.63960.63492.4988
Sum LVSI6.93576.68406.55085.2089
Maximum loadability (MW)856.92895.64872.74912.59