Implementation of Optimal Protection Coordination for Microgrids with Distributed Generations Using Quaternary Protection Scheme
Table 11
Dual-directional primary and backup relay operating times for quaternary scheme in islanded microgrid.
| DG operating status | Fault location | Operating times (t) of relay in second (Rp = primary relay; Rb = backup relay) | Rp | Rb1 | Rb2 |
| Status 1 | F-1 | R1 | R6 | R5 | 0.172 | 0.499 | 0.518 | R2 | R3 | R4 | 0.138 | 0.522 | 0.532 | F-2 | R3 | R2 | R1 | 0.259 | 0.532 | 0.553 | R4 | R5 | R6 | 0.152 | 0.439 | 0.461 | F-3 | R5 | R4 | R3 | 0.212 | 0.501 | 0.505 | R6 | R1 | R2 | 0.196 | 0.531 | 0.548 |
| Status 2 | F-1 | R1 | R6 | R5 | 0.144 | 0.484 | 0.497 | R2 | R3 | R4 | 0.540 | 0.787 | 0.805 | F-2 | R3 | R2 | R1 | 0.309 | 0.610 | 0.623 | R4 | R5 | R6 | 0.179 | 0.465 | 0.476 | F-3 | R5 | R4 | R3 | 0.406 | 0.715 | 0.728 | R6 | R1 | R2 | 0.264 | 0.564 | 0.578 |
| Status 3 | F-1 | R1 | R6 | R5 | 0.136 | 0.432 | 0.445 | R2 | R3 | R4 | 0.117 | 0.428 | 0.443 | F-2 | R3 | R2 | R1 | 0.514 | 0.828 | 0.837 | R4 | R5 | R6 | 0.219 | 0.509 | 0.530 | F-3 | R5 | R4 | R3 | 0.296 | 0.601 | 0.620 | R6 | R1 | R2 | 0.238 | 0.548 | 0.561 |
|
|