Implementation of Optimal Protection Coordination for Microgrids with Distributed Generations Using Quaternary Protection Scheme

Table 11

Dual-directional primary and backup relay operating times for quaternary scheme in islanded microgrid.

DG operating statusFault locationOperating times (t) of relay in second
(Rp = primary relay; Rb = backup relay)
RpRb1Rb2

Status 1F-1R1R6R5
0.1720.4990.518
R2R3R4
0.1380.5220.532
F-2R3R2R1
0.2590.5320.553
R4R5R6
0.1520.4390.461
F-3R5R4R3
0.2120.5010.505
R6R1R2
0.1960.5310.548

Status 2F-1R1R6R5
0.1440.4840.497
R2R3R4
0.5400.7870.805
F-2R3R2R1
0.3090.6100.623
R4R5R6
0.1790.4650.476
F-3R5R4R3
0.4060.7150.728
R6R1R2
0.2640.5640.578

Status 3F-1R1R6R5
0.1360.4320.445
R2R3R4
0.1170.4280.443
F-2R3R2R1
0.5140.8280.837
R4R5R6
0.2190.5090.530
F-3R5R4R3
0.2960.6010.620
R6R1R2
0.2380.5480.561