Implementation of Optimal Protection Coordination for Microgrids with Distributed Generations Using Quaternary Protection Scheme
Table 8
Directional primary and backup relay operating times for conventional scheme in islanded microgrid.
| DG operating status | Fault location | Operating times (t) of relay in second (Rp = primary relay; Rb = backup relay) | Rp | Rb1 | Rb2 |
| Status 1 | F-1 | R1 | R5 | R3 | 0.278 | 0.549 | 0.637 | R2 | R4 | R6 | 0.145 | 0.392 | 0.507 | F-2 | R3 | R1 | R5 | 0.210 | 0.438 | 0.466 | R4 | R6 | R2 | 0.259 | 0.490 | 0.518 | F-3 | R5 | R3 | R1 | 0.338 | 0.582 | 1.018 | R6 | R2 | R4 | 0.286 | 0.601 | 0.691 |
| Status 2 | F-1 | R1 | R5 | R3 | 0.278 | 1.106 | 1.188 | R2 | R4 | R6 | 0.203 | 0.995 | 1.139 | F-2 | R3 | R1 | R5 | 0.216 | 0.460 | 0.493 | R4 | R6 | R2 | 0.333 | 0.557 | 0.611 | F-3 | R5 | R3 | R1 | 0.508 | 0.873 | 0.893 | R6 | R2 | R4 | 0.291 | 0.517 | 0.556 |
| Status 3 | F-1 | R1 | R5 | R3 | 0.474 | 0.696 | 0.699 | R2 | R4 | R6 | 0.189 | 0.418 | 0.443 | F-2 | R3 | R1 | R5 | 0.616 | 2.000 | 2.010 | R4 | R6 | R2 | 0.283 | 1.090 | 1.102 | F-3 | R5 | R3 | R1 | 0.363 | 0.601 | 1.252 | R6 | R2 | R4 | 0.867 | 1.086 | 1.099 |
|
|