Implementation of Optimal Protection Coordination for Microgrids with Distributed Generations Using Quaternary Protection Scheme

Table 8

Directional primary and backup relay operating times for conventional scheme in islanded microgrid.

DG operating statusFault locationOperating times (t) of relay in second
(Rp = primary relay; Rb = backup relay)
RpRb1Rb2

Status 1F-1R1R5R3
0.2780.5490.637
R2R4R6
0.1450.3920.507
F-2R3R1R5
0.2100.4380.466
R4R6R2
0.2590.4900.518
F-3R5R3R1
0.3380.5821.018
R6R2R4
0.2860.6010.691

Status 2F-1R1R5R3
0.2781.1061.188
R2R4R6
0.2030.9951.139
F-2R3R1R5
0.2160.4600.493
R4R6R2
0.3330.5570.611
F-3R5R3R1
0.5080.8730.893
R6R2R4
0.2910.5170.556

Status 3F-1R1R5R3
0.4740.6960.699
R2R4R6
0.1890.4180.443
F-2R3R1R5
0.6162.0002.010
R4R6R2
0.2831.0901.102
F-3R5R3R1
0.3630.6011.252
R6R2R4
0.8671.0861.099