Implementation of Optimal Protection Coordination for Microgrids with Distributed Generations Using Quaternary Protection Scheme

Table 9

Dual-directional overcurrent relay settings for the quaternary protection coordination scheme.

RelayDG operatingGrid-connected microgrid in forward directionGrid-connected microgrid in reverse directionIslanded microgrid in forward directionIslanded microgrid in reverse direction
Is (pu)TMS (s)Is (pu)TMS (s)Is (pu)TMS (s)Is (pu)TMS (s)

R1Status 10.9089710.0500000.8304000.0500000.8707980.0655320.7740000.050000
Status 20.9200240.0500000.7520000.0500000.9267640.0507060.8120000.050000
Status 30.8167570.0500000.8917340.0500000.6511920.0578260.5781510.386953

R2Status 10.8428450.1348250.9614300.0505350.7743840.0965030.8923870.056220
Status 20.7720700.1289370.8321670.0500000.8139870.0948850.8229380.050000
Status 30.8512580.1182570.9702370.0500000.5524250.1928630.5821990.050016

R3Status 10.9229050.0500000.8702090.1438800.8414490.0500000.8578030.074514
Status 20.8089350.0500000.8880880.1207190.9029770.0500000.8030770.050000
Status 30.8597600.0500000.9294860.1397620.8956310.0501870.8199870.111881

R4Status 10.7380000.0578910.7710480.0500040.7611330.0563680.7670170.055154
Status 20.8475840.0777590.8694350.0500000.8040750.1674400.8591510.052559
Status 30.8117480.0500000.8504550.0500000.7698460.0500000.8806590.050052

R5Status 10.9902370.0563250.9012770.1157000.8337580.0527830.8906260.050322
Status 20.7292980.0500000.7280470.1596160.7964490.0500000.9015220.086345
Status 30.8185870.0500000.7260000.0641500.8696430.0565770.8010000.050000

R6Status 10.7396260.1029730.7774520.0502510.8117650.0500000.8697460.064470
Status 20.7502790.0788150.8505920.0500000.8000000.0500000.9537940.050007
Status 30.7151410.1227800.7605800.0500000.8607230.0847160.8100000.050000