Research Article

Static Voltage Stability Assessment of the Kenyan Power Network

Table 7

Loading margins and voltage stability margins of selected buses in critical modes.

Q-modeBUSLoading margin (MW)Loading margin (MVar)Active power-voltage stability marginReactive power-voltage stability margin

1Maungu15.566711.93770.40090.4739
Titanium21.314015.07400.39170.4231
Manyani14.668511.38660.39830.4720
Vipingo19.772314.84050.41850.4905
MSA cement33.569429.52460.49750.4941
Kilifi49.582440.19240.58950.5768
Jomvu29.922018.61530.43730.4312
Voi30.070223.51000.47890.5186
New Maungu40.790726.61910.52830.5438

2Ndhiwa19.821119.80890.46980.5143
Awendo26.654228.46060.48560.5379
Kisii29.486624.90270.46100.5065
Chemosit119.496212.13430.40010.4369
Chemosit217.01429.09830.34510.3726
Bomet24.076023.58060.47550.5201

3Sultan Hamud15.692911.32090.38540.4734
Mtito Andei14.062810.88540.39130.4684
Wote30.533228.05530.51210.5459
Ulu17.352213.26330.41450.4842
New Sultan Hamud36.868234.20710.56050.5858
Kiboko37.950831.31070.55150.5660

4Lokichar10.29778.66890.40980.4564
Kalemngorok14.083512.48280.44320.5188

5Garissa18.125117.82710.52320.5556
Mwingi27.971624.00120.52180.5713