Improvement of the Voltage Profile and Loss Reduction in Distribution Network Using Moth Flame Algorithm: Wolaita Sodo, Ethiopia
Table 3
Comparison results show location and rating of SVC and power loss reduction in 34-bus system.
| Techniques | MFA | PSO |
| Optimum placing of device | Bus 7 | Bus 11 | Optimal size of SVC | 2300 | 1352 kVAR | Active power loss (kW) | Without SVC | 210.99 | 369.57 kW | With SVC | 168.57 | 270.01 kW | % reduction in real power losses | 42.42 kW | 27.6 | Reactive power loss (kVAR) | Without SVC | 143.13 | 356.07 kVAR | With SVC | 126.26 | 260.12 kVAR | % reduction in reactive power losses | 16.87 kVAR | 27.4 kVAR | Computational time in sec | 0.65 sec | 1.145873 |
|
|