Improvement of the Voltage Profile and Loss Reduction in Distribution Network Using Moth Flame Algorithm: Wolaita Sodo, Ethiopia

Table 3

Comparison results show location and rating of SVC and power loss reduction in 34-bus system.

TechniquesMFAPSO

Optimum placing of deviceBus 7Bus 11
Optimal size of SVC23001352 kVAR
Active power loss (kW)Without SVC210.99369.57 kW
With SVC168.57270.01 kW
% reduction in real power losses42.42 kW27.6
Reactive power loss (kVAR)Without SVC143.13356.07 kVAR
With SVC126.26260.12 kVAR
% reduction in reactive power losses16.87 kVAR27.4 kVAR
Computational time in sec0.65 sec1.145873