Improvement of the Voltage Profile and Loss Reduction in Distribution Network Using Moth Flame Algorithm: Wolaita Sodo, Ethiopia

Table 7

Each line real and reactive power in the system run in backward/forward MATLAB.

LinePower at bus
FromTokWkVAr

12423.5981999.437
231342.361732.404
341725.7871061.465
45843.74971523.622
561188.4481233.752
671328.319662.9177
7828.9178996.4633
89962.906640.9058
910853.0899182.7174
1011728.5451623.197
1112559.4409262.6518
1213170.2558549.0849
131445.2561426.3698
1415111.1573108.7036
151691.66231.2216
161769.125728.6095
171822.945513.0193
21968.2395123.7001
192070.263.0337
202125.536537.6061
422109.423162.5714
222335.884100.9834
232460.74670.3374
242514.39340.5043
726147.9189193.5203
2627112.8311114.234
272891.46810.8508
282934.057529.744
1130130.5708150.9173
303131.660529.7673
1432107.5726105.7773
323384.373677.6234
333420.031611.9109