Research Article

STATCOM Controller Tuning to Enhance LVRT Capability of Grid-Connected Wind Power Generating Plants

Table 12

THD as a % of the fundamental value.

ParameterFault typeConventional STATCOM (%)PSO tuned STATCOM (%)WCA tuned STATCOM (%)WCA-PSO tuned STATCOM (%)

Vabc (B1)L-G5.664.84.623.92
LLL-G8.858.448.337.76

Iabc (B1)L-G24.5411.6711.938.84
LLL-G2.261.531.721.24