Research Article
Trust-Region Method for Load Flow Solution of Three-Phase Unbalanced Electric Power Distribution System
Table 7
Line impedance of 123-bus network.
| Conductor type | Impedance (ohm/mile) | a | b | c |
| 1 | a | 0.4576 + j1.0780 | 0.1560 + j0.5017 | 0.1535 + j0.3849 | b | 0.1560 + j0.5017 | 0.4666 + j1.0482 | 0.1580 + j0.4236 | c | 0.1560 + j0.5017 | 0.1580 + j0.4236 | 0.4615 + j1.0651 |
| 2 | a | 0.4666 + j1.0482 | 0.1580 + j0.4236 | 0.1560 + j0.5017 | b | 0.1580 + j0.4236 | 0.4615 + j1.0651 | 0.1535 + j0.3849 | c | 0.1560 + j0.5017 | 0.1535 + j0.3849 | 0.4576 + j1.0780 |
| 3 | a | 0.4615 + j1.0651 | 0.1535 + j0.3849 | 0.1580 + j0.4236 | b | 0.1535 + j0.3849 | 0.4576 + j1.0780 | 0.1560 + j0.5017 | c | 0.1580 + j0.4236 | 0.1560 + j0.5017 | 0.4666 + j1.0482 |
| 4 | a | 0.4615 + j1.0651 | 0.1580 + j0.4236 | 0.1535 + j0.3849 | b | 0.1580 + j0.4236 | 0.4666 + j1.0482 | 0.1560 + j0.5017 | c | 0.1535 + j0.3849 | 0.1560 + j0.5017 | 0.4576 + j1.0780 |
| 5 | a | 0.4666 + j1.0482 | 0.1560 + j0.5017 | 0.1580 + j0.4236 | b | 0.1560 + j0.5017 | 0.4576 + j1.0780 | 0.1535 + j0.3849 | c | 0.1580 + j0.4236 | 0.1535 + j0.3849 | 0.4615 + j1.0651 |
| 6 | a | 0.4576 + j1.0780 | 0.1535 + j0.3849 | 0.1560 + j0.5017 | b | 0.1535 + j0.3849 | 0.4615 + j1.0651 | 0.1580 + j0.4236 | c | 0.1560 + j0.5017 | 0.1580 + j0.4236 | 0.4666 + j1.0482 |
| 7 | a | 1.5209 + j0.7521 | 0.5198 + j0.2775 | 0.4924 + j0.2157 | b | 0.5198 + j0.2775 | 1.5329 + j0.7162 | 0.5198 + j0.2775 | c | 0.4924 + j0.2157 | 0.5198 + j0.2775 | 1.5209 + j0.7521 |
|
|