Research Article

Design of a Robust Coordinated Power Oscillation Damper for Use with Large-Scale Wind Energy System Connected to a Multimachine Power System

Table 4

Critical oscillation modes considering the PSSs only.

Operating scenarioModeEigenvalueFrequency (Hz)Damping ratio (%)Participating generators

1M1−0.5917 ± j12.72682.0264.64WG
M2−1.9960 ± j8.71601.38722.32G3, G4
M3−0.9419 ± j4.84890.77219.07All G

2M1−0.5165 ± j12.73732.0274.05WG
M2−2.2823 ± j8.39301.33626.24G3, G4
M3−0.6929 ± j4.23380.67416.15All G

3M1−0.5162 ± j12.73682.0274.05WG
M2−2.3802 ± j7.98151.27028.58G3, G4
M3−0.3196 ± j3.25280.5189.77All G