Design of a Robust Coordinated Power Oscillation Damper for Use with Large-Scale Wind Energy System Connected to a Multimachine Power System
Table 7
The oscillation modes with uncoordinated design of POD.
| Operating scenario | Mode | Eigenvalue | Frequency (Hz) | Damping ratio (%) | Participating generators |
| 1 | M1 | −2.3476 ± j10.8467 | 1.726 | 21.15 | WG | M2 | −1.9961 ± j8.7160 | 1.387 | 22.32 | G3, G4 | M3 | −0.9418 ± j4.8491 | 0.772 | 19.07 | All G |
| 2 | M1 | −2.3200 ± j11.0844 | 1.764 | 20.49 | WG | M2 | −2.2822 ± j8.3929 | 1.336 | 26.24 | G3, G4 | M3 | −0.6928 ± j4.2339 | 0.674 | 16.15 | All G |
| 3 | M1 | −2.3543 ± j11.0934 | 1.766 | 21.15 | WG | M2 | −2.3803 ± j7.9814 | 1.270 | 28.58 | G3, G4 | M3 | −0.3196 ± j3.2529 | 0.518 | 9.78 | All G |
|
|