Design of a Robust Coordinated Power Oscillation Damper for Use with Large-Scale Wind Energy System Connected to a Multimachine Power System
Table 9
The oscillation modes with the coordinated design of POD and PSSs.
| Operating scenario | Mode | Eigenvalue | Frequency (Hz) | Damping ratio (%) | Participating generators |
| 1 | M1 | −2.3677 ± j10.9968 | 1.750 | 21.05 | WG | M2 | −4.1695 ± j11.5795 | 1.843 | 33.88 | G3, G4 | M3 | −4.2083 ± j2.7386 | 0.438 | 83.8 | All G |
| 2 | M1 | −2.4521 ± j11.2703 | 1.794 | 21.26 | WG | M2 | −4.2521 ± j11.1357 | 1.772 | 35.66 | G3, G4 | M3 | −3.6147 ± j3.6181 | 0.576 | 70.68 | All G |
| 3 | M1 | −2.5035 ± j11.2761 | 1.795 | 21.67 | WG | M2 | −4.6042 ± j10.6739 | 1.699 | 39.61 | G3, G4 | M3 | −2.7855 ± j3.6703 | 0.584 | 60.45 | All G |
|
|