Table of Contents Author Guidelines Submit a Manuscript
Journal of Healthcare Engineering
Volume 1 (2010), Issue 4, Pages 655-674
Research Article

Airborne Contamination Control through Directed Airflow in the Exam Room: A Pilot Study Using a Membrane Diffuser

Debajyoti Pati,1 Michael P. Pietrzak,1 David Duthu,2 Ting-Kwo George Lei,3 David Vincent,1 Tom Franklin,2 Thomas E. Harvey Jr.,1 and Troy Ransdell1

1HKS Architects, 1919 McKinney Avenue, Dallas, TX, USA
2CCRD Partners, 808 Travis Street Suite 200, Houston, TX, USA
3Fluid Dynamics Solutions, Inc., 12453 S.E. Mountain Sun Lane, Clackamas, OR, USA

Copyright © 2010 Hindawi Publishing Corporation. This is an open access article distributed under the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.


Airborne infections have been documented as a major source of hospital acquired infection - one of the major concerns in healthcare delivery. An important factor contributing to airborne infection is cross contamination through air particulate dispersion as affected by the ventilation system design. Clean room technology (with membrane ceiling) has been successfully used in technology and pharmaceutical industries to control airborne contamination. This study examined the performance of membrane ceiling technology in controlling air particulate dispersion in a mock-up exam room. It included both performance tests in a mock-up room and a simulation study of six different ventilation system designs using Computational Fluid Dynamics (CFD) analysis. Findings suggest that a membrane diffuser directed airflow ventilation strategy occupying approximately 20% to 30% of the ceiling surface and placed over the patient in a contemporary sized exam room provides a less turbulent airflow pattern and less mixing of the air between the patient and others in the room.