Influence of the Arrangement of Surgical Light Axes on the Air Environment in Operating Rooms
Table 1
Outlines of operating rooms.
| ā | Single axis (No. 17) | Double axis (No. 16) |
| Width (m) | 6.1 | 6.1 | Distance (m) | 5.45 | 5.45 | Floor space (m2) | 34.22 | 34.22 | Ceiling height (m) | 3.0 | 3.0 | Room volume (m3) | 102.7 | 102.7 | Designed outdoor air intake volume (m3/h) | 920 | 920 | Designed total airflow volume (m3/h) | 6,300 | 6,000 | Air-conditioning outlet filter area (m2) | 3.163 | 3.535 | Designed outlet flow velocity (m/s) | 0.553 | 0.471 | Measured outlet flow velocity (m/s) | 0.55 | 0.40 |
|
|