Planning and Design of Low-Power-Consuming Full-Outer-Air-Intake Natural Air-Conditioning System

Table 2

Comparison table of the building energy conversion system and traditional total heat exchanger system.

ItemThis subjected systemTotal heat exchanger
Rotary wheelPolymer fixed plate

Energy conversion methodAir and waterAirAir
Fan powerVariable air volumeConstant air volumeConstant air volume
Equipment powerFan and pumpWheel motor and fanFan
Separation of intake/exhaust airEntirely separatedMixed upSeparated by highly permeable fibers
Air cross-contaminationNoYesYes
Positive/negative environmentYesNoNo
Sensible energy conversion efficiency71%∼112%65%∼78%65%∼78%
EER24.87∼13.69 kcal/W·hN/A5.43∼0.07 kcal/W·h

N/A: unable to measure EER because the wheel-type total heat exchanger does not provide a similar model.