Research Article
A Gas Monitoring and Control System in a Coal and Gas Outburst Laboratory
Table 1
Gas threshold and measures.
| Degree of risk | Sensor | Gas content threshold | Measure | Monitoring area |
| Normal | 1, 2 | CH4 ≤ 0.025% | No measure | Entire laboratory | Danger 1 | 1 | CH4 = 0.025% | Attention and Ventilation 1 | Unsafe zone | Danger 2 | 1 | CH4 = 1% | Alarm and Ventilation 2 | Unsafe zone | Danger 3 | 2 | CH4 = 0.025% | Alarm and Ventilation 3 | Entire laboratory | Danger 4 | 2 | CH4 = 1% | Power off and evacuation | Entire laboratory |
|
|