Research Article

Faulty Line Selection Method for Distribution Network Based on Variable Scale Bistable System

Table 2

Results of different initial angle and ground resistance.

Faulty lineFault situationJudgment result

(0°, 10 Ω)0.49420.80540.90920.78520.60780.7973 fault
(0°, 100 Ω)0.67760.73600.75280.85730.70340.8744 fault
(0°, 500 Ω)0.57100.71460.65490.89990.83690.9032 fault
(0°, 1000 Ω)0.59910.35110.72910.78100.74240.6944 fault
(0°, 1500 Ω)0.68450.27960.33300.70570.59930.8385 fault
(0°, 2000 Ω)0.69280.53820.55110.64650.52930.8454 fault
(30°, 10 Ω)0.58350.82950.93600.81320.63620.7710 fault
(30°, 100 Ω)0.77670.89680.89480.86680.72650.8485 fault
(30°, 500 Ω)0.79870.88580.87730.87460.86090.9254 fault
(30°, 1000 Ω)0.73530.63730.79270.85980.90000.7555 fault
(30°, 1500 Ω)0.69720.54620.58190.82330.74780.8720 fault
(30°, 2000 Ω)0.73400.47460.49870.81160.70520.8649 fault
(60°, 10 Ω)0.61130.84180.96060.82010.61090.7682 fault
(60°, 100 Ω)0.85230.93980.97030.90800.74610.8808 fault
(60°, 500 Ω)0.90270.98220.94070.92680.90150.9374 fault
(60°, 1000 Ω)0.88620.74250.94200.86390.93680.7823 fault
(60°, 1500 Ω)0.91370.73220.73020.84500.78470.8721 fault
(60°, 2000 Ω)0.88550.91290.88720.80270.72840.8894 fault
(90°, 10 Ω)0.92930.87280.96910.91170.87950.7960 fault
(90°, 100 Ω)0.94640.97900.98200.95490.88790.9346 fault
(90°, 500 Ω)0.97140.85780.99320.89900.94870.8150 fault
(90°, 1000 Ω)0.98460.85240.84280.84670.79320.8995 fault
(90°, 1500 Ω)0.98120.84570.79700.80330.72650.9038 fault
(90°, 2000 Ω)0.97320.80920.75350.74080.65970.9216 fault