Detection of Dissolved Carbon Monoxide in Transformer Oil Using 1.567 m Diode Laser-Based Photoacoustic Spectroscopy

Table 1

Measurement results detected by PAS and GA.

CO concentrationPAS (L/L)GA (L/L)Detection error (%)

Sample 15019.45003.80.31
Sample 22012.72000.60.61
Sample 31011.51002.30.92
Sample 4860.9851.71.08
Sample 5682.1673.91.22
Sample 6559.8550.21.75