UPFC Location and Performance Analysis in Deregulated Power Systems
Table 2
OPF cost increase due to the addition of UPFC series part impedance.
| line | impedance | sending end | receiving end | | | | | | | (pu) | (pu) | (/hrpu) | (pu) | (pu) | (/hrpu) | (pu) |
| 1-2 | 0.050 | 8.52 | 215.9 | 10.79 | 9.56 | 251.7 | 12.59 | 1-4 | 0.022 | 74.20 | 2549 | 56.60 | 80.07 | 2742 | 60.87 | 1-5 | 0.050 | 4.73 | 619 | 30.96 | 3.79 | 697.8 | 34.89 | 2-3 | 0.050 | 1.52 | 32.7 | 1.64 | 1.12 | 30.46 | 1.52 | 2-4 | 0.022 | 33.11 | 3121 | 69.28 | 33.64 | 3212 | 71.31 | 2-5 | 0.089 | 59.54 | 472.9 | 42.04 | 72.89 | 540.2 | 48.03 | 2-6 | 0.010 | 3.92 | 354.6 | 3.51 | 4.59 | 411.1 | 4.07 | 3-5 | 0.016 | 4.25 | 217.8 | 3.55 | 5.07 | 259.5 | 4.23 | 3-6 | 0.013 | 4.78 | 295.7 | 3.70 | 4.83 | 295.9 | 3.70 | 4-5 | 0.200 | 0.24 | 5.81 | 1.16 | 14.60 | 110.6 | 22.12 | 5-6 | 0.050 | 3.23 | 67.27 | 3.36 | 0.69 | 12.41 | 0.62 |
|
|