Research Article
A New Algorithm for the Available Transfer Capability Determination
Table 6
Results of area-to-area ATC due to transient stability limit.
| Area of transfers | Limiting generator | ATC (MW) | CPU time (minute) |
Number of load flow solutions | Selling area | Buying area | Bus | Generator unit | Ralston’s with cubic-spline | Recursive AC power flow | Ralston’s with cubic-spline | Recursive AC power flow | Ralston’s with cubic-spline | Recursive AC power flow |
| 1 | 2 | 32 | G3 | 448 | 449 | 0.03 | 1.37 | 18 | 449 | 1 | 3 | 32 | G3 | 449 | 449 | 0.03 | 1.20 | 18 | 449 | 2 | 1 | 34 | G5 | 858 | 857 | 0.03 | 1.81 | 18 | 857 | 2 | 3 | 34 | G5 | 870 | 870 | 0.03 | 2.20 | 18 | 870 | 3 | 1 | 38 | G9 | 660 | 660 | 0.08 | 1.62 | 18 | 660 | 3 | 2 | 38 | G9 | 723 | 722 | 0.03 | 1.90 | 18 | 722 |
|
|