39-New England bus system data.
| Bus | Type | Load | Generator | Voltage (P.U) | MW | MVAR | MW | MVAR |
| 1 | Slack | 9.2 | 4.6 | 0 | 0 | 0.9820 | 2 | PQ | 0.0 | 0.0 | 0 | 0 | 1.0 | 3 | PQ | 322 | 2.4 | 0 | 0 | 1.0 | 4 | PQ | 500 | 184 | 0 | 0 | 1.0 | 5 | PQ | 0.0 | 0.0 | 0 | 0 | 1.0 | 6 | PQ | 0.0 | 0.0 | 0 | 0 | 1.0 | 7 | PQ | 233.8 | 84 | 0 | 0 | 1.0 | 8 | PQ | 522 | 176 | 0 | 0 | 1.0 | 9 | PQ | 0.0 | 0.0 | 0 | 0 | 1.0 | 10 | PQ | 0.0 | 0.0 | 0 | 0 | 1.0 | 11 | PQ | 0.0 | 0.0 | 0 | 0 | 1.0 | 12 | PQ | 7.5 | 88 | 0 | 0 | 1.0 | 13 | PQ | 0.0 | 0.0 | 0 | 0 | 1.0 | 14 | PQ | 0.0 | 0.0 | 0 | 0 | 1.0 | 15 | PQ | 320 | 153 | 0 | 0 | 1.0 | 16 | PQ | 329 | 32.3 | 0 | 0 | 1.0 | 17 | PQ | 0.0 | 0.0 | 0 | 0 | 1.0 | 18 | PQ | 158 | 30 | 0 | 0 | 1.0 | 19 | PQ | 0.0 | 0.0 | 0 | 0 | 1.0 | 20 | PQ | 628 | 103 | 0 | 0 | 1.0 | 21 | PQ | 274 | 115 | 0 | 0 | 1.0 | 22 | PQ | 0.0 | 0.0 | 0 | 0 | 1.0 | 23 | PQ | 247.5 | 84.6 | 0 | 0 | 1.0 | 24 | PQ | 308.6 | | 0 | 0 | 1.0 | 25 | PQ | 224 | 47.2 | 0 | 0 | 1.0 | 26 | PQ | 139 | 17 | 0 | 0 | 1.0 | 27 | PQ | 281 | 75.5 | 0 | 0 | 1.0 | 28 | PQ | 206 | 27.6 | 0 | 0 | 1.0 | 29 | PQ | 283.5 | 26.9 | 0 | 0 | 1.0 | 30 | PV | 0.0 | 0.0 | 250 | 0 | 1.0475 | 31 | PQ | 0.0 | 0.0 | 0 | 0 | 1.0 | 32 | PV | 0.0 | 0.0 | 650 | 0 | 0.9831 | 33 | PV | 0.0 | 0.0 | 632 | 0 | 0.9972 | 34 | PV | 0.0 | 0.0 | 508 | 0 | 1.0123 | 35 | PV | 0.0 | 0.0 | 650 | 0 | 1.0493 | 36 | PV | 0.0 | 0.0 | 560 | 0 | 1.0635 | 37 | PV | 0.0 | 0.0 | 540 | 0 | 1.0278 | 38 | PV | 0.0 | 0.0 | 830 | 0 | 1.0265 | 39 | PV | 1104 | 250 | 1000 | 0 | 1.03 |
|
|