Optimal Protection Coordination for Microgrid under Different Operating Modes

Table 2

Fault currents of bolted three-phase faults in utility-only mode and in grid-connected mode.

Location of faultRelay Fault current (A)
(utility-only mode)
Fault current (A)
(grid-connected mode)
PrimaryBackupPrimaryBackupPrimaryBackup

F1FCB2Main CB111,68711,68712,10412,048
F2FCB3Main CB111,68711,68712,12312,086
F3LCB4FCB27,6087,6037,3217,305
F4LCB5FCB25,6125,5885,5935,300
F5LCB6FCB24,4464,3993,8864,231
F6LCB7FCB37,6087,6037,2287,016
F7LCB8FCB35,6125,5885,2985,075
F8LCB9FCB34,4464,3994,2083,938
F9CB10LCB45,6725,6684,7374,731
F10CB11LCB54,4834,4803,8813,882
F11CB12LCB75,6725,6684,8264,823
F12CB13LCB84,4834,4803,7063,706