Optimal Protection Coordination for Microgrid under Different Operating Modes
Table 4
Optimal TDSs of the CO relays.
| Relay | CT ratio | Tap | TDS | Utility-only mode | Grid-connected mode |
| Main CB1 | 2000/5 | 5.0 | 0.458 | 0.451 | FCB2 | 600/5 | 5.0 | 1.250 | 1.125 | FCB3 | 600/5 | 5.0 | 1.250 | 1.074 | LCB4 | 1000/1 | 0.38 | 0.900 | 0.770 | LCB5 | 1000/1 | 0.38 | 0.700 | 0.600 | LCB6 | 1000/1 | 0.38 | 0.080 | 0.080 | LCB7 | 1000/1 | 0.38 | 0.900 | 0.770 | LCB8 | 1000/1 | 0.38 | 0.700 | 0.509 | LCB9 | 1000/1 | 0.38 | 0.080 | 0.080 | CB10 | 1000/1 | 0.17 | 0.080 | 0.080 | CB11 | 1000/1 | 0.17 | 0.080 | 0.080 | CB12 | 1000/1 | 0.17 | 0.080 | 0.080 | CB13 | 1000/1 | 0.17 | 0.080 | 0.080 |
|
|