Optimal Protection Coordination for Microgrid under Different Operating Modes
Table 5
Relay operating times for bolted three-phase faults in utility-only mode and in grid-connected mode.
| Primary relay | Back-up relay | Operating time (sec) | Utility-only mode | Grid-connected mode | Primary | Backup | CTI | Primary | Backup | CTI |
| FCB2 | Main CB1 | 0.245 | 0.445 | 0.2 | 0.215 | 0.415 | 0.2 | FCB3 | Main CB1 | 0.245 | 0.445 | 0.2 | 0.205 | 0.413 | 0.208 | LCB4 | FCB2 | 0.173 | 0.373 | 0.2 | 0.152 | 0.352 | 0.2 | LCB5 | FCB2 | 0.176 | 0.563 | 0.387 | 0.151 | 0.548 | 0.397 | LCB6 | FCB2 | 0.026 | 0.820 | 0.794 | 0.031 | 0.787 | 0.756 | LCB7 | FCB3 | 0.173 | 0.373 | 0.2 | 0.153 | 0.353 | 0.2 | LCB8 | FCB3 | 0.176 | 0.563 | 0.387 | 0.136 | 0.560 | 0.424 | LCB9 | FCB3 | 0.026 | 0.820 | 0.794 | 0.028 | 0.850 | 0.822 | CB10 | LCB4 | 0.011 (0.015)* | 0.224 | 0.213 (0.209) | 0.012 (0.015) | 0.234 | 0.222 (0.219) | CB11 | LCB5 | 0.012 (0.015) | 0.228 | 0.216 (0.213) | 0.014 (0.015) | 0.236 | 0.222 (0.221) | CB12 | LCB7 | 0.011 (0.015) | 0.224 | 0.213 (0.209) | 0.012 (0.015) | 0.229 | 0.217 (0.214) | CB13 | LCB8 | 0.012 (0.015) | 0.228 | 0.216 (0.213) | 0.014 (0.015) | 0.215 | 0.201 (0.200) |
|
|
The corrected values are shown in parentheses.
|