Research Article
Optimal Protection Coordination for Microgrid under Different Operating Modes
Table 6
Optimal TDSs of the LCO relays.
| Relay | CT ratio | Tap | TDS | Utility-only mode | Grid-connected mode |
| Main CB1 | 2000/5 | 2.0 | 1.100 | 1.100 | FCB2 | 600/5 | 2.0 | 1.968 | 1.923 | FCB3 | 600/5 | 2.0 | 1.968 | 1.890 | LCB4 | 1000/1 | 0.15 | 0.750 | 0.730 | LCB5 | 1000/1 | 0.15 | 0.690 | 0.655 | LCB6 | 1000/1 | 0.15 | 0.100 | 0.100 | LCB7 | 1000/1 | 0.15 | 0.750 | 0.727 | LCB8 | 1000/1 | 0.15 | 0.690 | 0.636 | LCB9 | 1000/1 | 0.15 | 0.100 | 0.100 |
|
|