Research Article

Optimal Protection Coordination for Microgrid under Different Operating Modes

Table 7

Operating times and CTIs for bolted single line-to-ground faults in utility-only mode and in grid-connected mode.

Primary relayBack-up relayOperating time (sec)
Utility-only modeGrid-connected mode
PrimaryBackupCTIPrimaryBackupCTI

FCB2Main CB10.261 (0.379)*0.636 (0.636)0.375 (0.257)0.256 (0.370)0.637 (0.636)0.381 (0.266)
FCB3Main CB10.261 (0.377)0.636 (0.636)0.375 (0.259)0.253 (0.364)0.637 (0.636)0.384 (0.272)
LCB4FCB20.100 (0.144)0.300 (0.379)0.2 (0.235)0.099 (0.140)0.299 (0.370)0.2 (0.23)
LCB5FCB20.101 (0.133)0.365 (0.379)0.264 (0.246)0.099 (0.126)0.372 (0.384)0.273 (0.258)
LCB6FCB20.016 (0.019)0.458 (0.461)0.442 (0.442)0.017 (0.019)0.463 (0.467)0.446 (0.448)
LCB7FCB30.100 (0.144)0.300 (0.379)0.2 (0.235)0.099 (0.140)0.299 (0.358)0.2 (0.218)
LCB8FCB30.101 (0.133)0.365 (0.379)0.264 (0.246)0.099 (0.122)0.380 (0.381)0.281 (0.259)
LCB9FCB30.016 (0.019)0.458 (0.461)0.442 (0.442)0.018 (0.019)0.496 (0.505)0.478 (0.486)

The corrected values are shown in parentheses.