Research Article

Optimal Protection Coordination for Microgrid under Different Operating Modes

Table 9

The taps and TDSs for all IEDs in islanding mode.

RelayCT ratioTap of CO Tap of LCOTDS

FCB2600/52.542.562
FCB3600/52.402.42
LCB41000/10.330.10
LCB51000/10.360.35
LCB61000/10.330.27
LCB71000/10.380.13
LCB81000/10.410.15
LCB91000/10.440.19
CB101000/10.280.09
CB111000/10.300.13
CB121000/10.320.07
CB131000/10.350.08