Mathematical Problems in Engineering / 2013 / Article / Tab 1

Research Article

Modeling Analysis of Power Transformer Fault Diagnosis Based on Improved Relevance Vector Machine

Table 1

Sample group of dissolved gases.

No.Fault typeData of gas content (unit: ppm)
H2CH4C2H6C2H4C2H2

1 Overheating7452314212006
2 Overheating22038282101917
3 Overheating116352904655
4 High energy discharge295 5112117124
5 High energy discharge4498312104176
6 Low energy discharge5669235462
7 Low energy discharge1525432203
8 Low energy discharge 1727836286
9 No fault 53266
10 No fault 676136

We are committed to sharing findings related to COVID-19 as quickly as possible. We will be providing unlimited waivers of publication charges for accepted research articles as well as case reports and case series related to COVID-19. Review articles are excluded from this waiver policy. Sign up here as a reviewer to help fast-track new submissions.