Research Article
Modeling Analysis of Power Transformer Fault Diagnosis Based on Improved Relevance Vector Machine
Table 1
Sample group of dissolved gases.
| No. | Fault type | Data of gas content (unit: ppm) | H2 | CH4 | C2H6 | C2H4 | C2H2 |
| 1 | Overheating | 74 | 523 | 142 | 1200 | 6 | 2 | Overheating | 220 | 382 | 82 | 1019 | 17 | 3 | Overheating | 116 | 352 | 90 | 465 | 5 | 4 | High energy discharge | 295 | 51 | 12 | 117 | 124 | 5 | High energy discharge | 449 | 83 | 12 | 104 | 176 | 6 | Low energy discharge | 566 | 92 | 35 | 46 | 2 | 7 | Low energy discharge | 152 | 54 | 32 | 20 | 3 | 8 | Low energy discharge | 172 | 78 | 36 | 28 | 6 | 9 | No fault | 5 | 3 | 2 | 6 | 6 | 10 | No fault | 6 | 7 | 6 | 13 | 6 |
|
|