Research Article
Fault Diagnosis of Oil-Immersed Transformers Using Self-Organization Antibody Network and Immune Operator
Table 4
Diagnosis results of test samples.
| Fault type | Number of testing samples | Classification results | Diagnostic accuracy/% | T1 | T2 | T3 | D1 | D2 | PD |
| T1 | 17 | 14 | 1 | 2 | 0 | 0 | 0 | 82.35 | T2 | 25 | 1 | 21 | 2 | 1 | 0 | 0 | 84.00 | T3 | 34 | 2 | 2 | 28 | 1 | 1 | 0 | 82.35 | D1 | 26 | 0 | 0 | 1 | 22 | 2 | 1 | 84.62 | D2 | 20 | 0 | 0 | 0 | 1 | 18 | 1 | 90.00 | PD | 15 | 0 | 0 | 0 | 2 | 0 | 13 | 86.67 |
|
|