A Novel Fault Line Selection Method Based on Improved Oscillator System of Power Distribution Network
Table 7
High resistance to ground fault result.
| Fault line | Fault situation | Distance of phase trajectory | | | | | Selection result |
| | (0°, 1500 Ω) | | 0.0546 | 1.4653 | 1.4695 | 1.4687 | Failure | | 0.0027 | 0.0076 | 0.0362 | 0.0376 | (0°, 1700 Ω) | | 0.1191 | 0.0052 | 1.4749 | 1.4676 | Failure | | 0.0025 | 0.0017 | 0.0342 | 0.0548 | (0°, 1800 Ω) | | 0.0014 | 1.4679 | 1.4679 | 1.4672 | Failure | | 0.0001 | 0.0010 | 0.0175 | 0.0402 | (0°, 1900 Ω) | | 0.0114 | 1.4658 | 1.4704 | 1.4675 | Failure | | 0.0017 | 0.0060 | 0.0241 | 0.0271 | (0°, 2000 Ω) | | 0.0569 | 0.0007 | 0.0550 | 1.4669 | Failure |
|
|