Modified Quasi-Steady State Model of DC System for Transient Stability Simulation under Asymmetric Faults
Table 6
Steady state DC values and errors during the 100 ms double phase-grounded fault for QSS and MQSS models.
| Double phase-grounded resistance () | Parameters | EMT model (pu) | QSS model (pu) | Modified model (pu) | Relative error of QSS model (%) | Relative error of modified model (%) |
| 60 | | 0.6500 | 0.8500 | 0.7470 | 30.77 | 14.92 | | 0.4800 | 0.7400 | 0.6217 | 54.17 | 29.31 | | 0.4750 | 0.7250 | 0.6380 | 52.63 | 34.32 |
| 80 | | 0.7050 | 0.8840 | 0.7069 | 25.39 | 0.27 | | 0.5700 | 0.7790 | 0.5733 | 36.67 | 5.79 | | 0.5750 | 0.7800 | 0.6424 | 35.65 | 11.72 |
| 100 | | 0.7900 | 0.9200 | 0.8104 | 16.46 | 2.58 | | 0.6500 | 0.8000 | 0.6486 | 23.08 | 0.22 | | 0.6520 | 0.8150 | 0.6623 | 25.00 | 1.58 |
|
|