Research Article

A Model of Intelligent Fault Diagnosis of Power Equipment Based on CBR

Table 2

Classification of transformer condition.

NumberConditionClass codeReason

1OKNormal status of transformer.
2Low energy dischargeAn intermittent discharge failure, such as potential discharge caused by poor contact discharge between the laminations, core and ground, and core and screw mandrel.
3High energy dischargeHigh energy discharge means internal flashover caused by insulation breakdown between the coils and the overvoltage, flashover caused by lead fracture, and arcing faults caused by tap arcing or capacitive screen breakdown.
4Partial dischargeIt often occurs in the gas cavity and suspension charged body; its characteristic gas is hydrogen and methane, even a small amount of acetylene in high discharge energy density.
5Low temperature thermalSolid insulation suffers long-time low temperature overheat caused by overload or other reasons.
6High temperature thermalInsulating oil decomposes since inside heat is caused by equipment failure, and the reasons include tap poor contact, weak weld between leads and connections tap, and core multipoint grounding and partial short circuit.