Research Article
Study on Engineering Design and Cost Performance of Borehole Heat Exchangers
Table 2
Parameters of the heat pump unit of GSHP system.
| Operating mode | Cooling/heating capacity (kW) | Temperature of U-tube circulating liquid (°C) | Temperature of cooling water (°C) | Pressure drop of evaporator (kPa) | Pressure drop of condenser (kPa) | Electricity consumption (kW) |
| Cooling | 1130 | 12/7 | 15/23 | 98 | 13.7 | 193 | Heating | 1473 | 50/45 | 15/10 | 98 | 13.7 | 336 |
|
|