Research Article

A Fault Diagnosis Method of High Voltage Circuit Breaker Based on Moving Contact Motion Trajectory and ELM

Table 2

Feature extraction of circuit breaker in various conditions.

StatusCHV
MT (ms)CD (mm)OT (mm)OS (mm)OV (mm)CV (m/s)

Normal close96.18215.277133.6213.206118.3443.42
96.70615.125132.3172.891117.1923.61
97.23714.324132.6952.796118.3713.29

Mechanism jam79.3858.468108.2191.89599.7512.81
77.1848.652110.5471.589101.8953.05
85.98210.626122.5241.967111.8982.58

Operating mechanism loosening102.54611.338140.8452.166129.5072.34
110.36112.466145.7842.452133.3182.35
115.96212.989148.8662.578135.8772.35