Research Article
A Fault Diagnosis Method of High Voltage Circuit Breaker Based on Moving Contact Motion Trajectory and ELM
Table 2
Feature extraction of circuit breaker in various conditions.
| Status | CHV | MT (ms) | CD (mm) | OT (mm) | OS (mm) | OV (mm) | CV (m/s) |
| Normal close | 96.182 | 15.277 | 133.621 | 3.206 | 118.344 | 3.42 | 96.706 | 15.125 | 132.317 | 2.891 | 117.192 | 3.61 | 97.237 | 14.324 | 132.695 | 2.796 | 118.371 | 3.29 |
| Mechanism jam | 79.385 | 8.468 | 108.219 | 1.895 | 99.751 | 2.81 | 77.184 | 8.652 | 110.547 | 1.589 | 101.895 | 3.05 | 85.982 | 10.626 | 122.524 | 1.967 | 111.898 | 2.58 |