Research Article
Reconfiguration of Distribution Networks with Distributed Generation Using a Dual Hybrid Particle Swarm Optimization Algorithm
Table 1
Reconfiguration results without DG connected into grid.
| Reconfiguration condition | Disconnect network switch | Minimum node voltage | Network loss/kW |
| Before reconfiguration | 8-21 9-15 12-22 18-33 25-29 | 0.9185 | 202.65 | Literature | 7-8 9-10 14-15 28-29 32-33 | 0.9412 | 139.90 | Algorithm in this paper | 7-8 9-10 14-15 25-29 32-33 | 0.9378 | 139.47 |
|
|