Research Article

Data-Driven Fault Diagnosis Method for Power Transformers Using Modified Kriging Model

Table 3

Some test results (μL/L).

Serial numberH2CH4C2H6C2H4C2H2Fault type
Actual faultFault analysis

()935843370Middle temperature overheatingMiddle temperature overheating
()139526.8639.6Middle and low temperature overheatingMiddle temperature overheating
()19.6320.7279.2574.70High temperature overheatingHigh temperature overheating
()45779541902.4High temperature overheatingHigh temperature overheating
()2794118.14231.8High energy dischargeHigh energy discharge
()14.673.6810.542.710.2NormalNormal
()345112.2527.551.558.75Low energy dischargeLow energy discharge
()217.5404.951.867.5High energy dischargeHigh energy discharge
()1812622105280Middle and low temperature overheatingLow temperature overheating
()44.317.33.623.310.4High energy dischargeHigh energy discharge
()172.9334.1172.9812.537.7Partial dischargePartial discharge
()12.268.8613.9518.210NormalLow energy discharge
()5678181730Low temperature overheatingLow temperature overheating