Research Article
Data-Driven Fault Diagnosis Method for Power Transformers Using Modified Kriging Model
Table 3
Some test results (μL/L).
| Serial number | H2 | CH4 | C2H6 | C2H4 | C2H2 | Fault type | Actual fault | Fault analysis |
| () | 93 | 58 | 43 | 37 | 0 | Middle temperature overheating | Middle temperature overheating | () | 139 | 52 | 6.8 | 63 | 9.6 | Middle and low temperature overheating | Middle temperature overheating | () | 19.6 | 320.7 | 279.2 | 574.7 | 0 | High temperature overheating | High temperature overheating | () | 457 | 79 | 54 | 190 | 2.4 | High temperature overheating | High temperature overheating | () | 279 | 41 | 18.1 | 42 | 31.8 | High energy discharge | High energy discharge | () | 14.67 | 3.68 | 10.54 | 2.71 | 0.2 | Normal | Normal | () | 345 | 112.25 | 27.5 | 51.5 | 58.75 | Low energy discharge | Low energy discharge | () | 217.5 | 40 | 4.9 | 51.8 | 67.5 | High energy discharge | High energy discharge | () | 181 | 262 | 210 | 528 | 0 | Middle and low temperature overheating | Low temperature overheating | () | 44.3 | 17.3 | 3.6 | 23.3 | 10.4 | High energy discharge | High energy discharge | () | 172.9 | 334.1 | 172.9 | 812.5 | 37.7 | Partial discharge | Partial discharge | () | 12.26 | 8.86 | 13.95 | 18.21 | 0 | Normal | Low energy discharge | () | 56 | 78 | 18 | 173 | 0 | Low temperature overheating | Low temperature overheating |
|
|