A Novel Protection Scheme against Fault Resistance for AC Microgrid

Table 3

Active power values and the protection threshold setting values of various types of FTFR in different internal fault positions under islanded mode.

Islanded modeTypes of faultFault position (MW)
side25%50%75% side

ABG (5 Ω, 5 Ω)1.05 (0.13)0.26 (0.10)0.12 (0.08)0.22 (0.08)0.97 (0.07)
ABG (5 Ω, 6 Ω)0.93 (0.10)0.17 (0.08)0.04 (0.02)0.16 (0.018)0.89 (0.016)
AB (5 Ω)0.30 (0.07)0.16 (0.04)0.11 (0.03)0.14 (0.03)0.26 (0.02)
AG (5 Ω)0.51 (0.10)0.10 (0.03)0.04 (0.02)0.09 (0.019)0.50 (0.018)
ABCG (4 Ω, 5 Ω, 6 Ω)0.91 (0.15)0.30 (0.08)0.03 (0.014)0.26 (0.014)0.83 (0.013)

ABCG (5 Ω, 5 Ω, 5 Ω)0.97 (0.16)0.36 (0.09)0.13 (0.058)0.32 (0.055)0.96 (0.05)