Table 5

Parameter of 115 kV transmission line and tower.

Tower characteristic

Tower NameDA1

Conductor size795 MCM ACSR/GA

Ruling span330 m. (Distance from tower to tower)

Conductor characteristic

Size795 MCM ACSR/GA

Diameter26.80 mm.

Number of conductors1 conductor per bundle

Current capacity845 A per conductor

Max. sag of conductor10.55 m.

Overhead ground wire characteristic

Size3/8” (HS) Galvanized steel

Diameter9.144 mm.

Number of conductors1 conductor