Complementary Ventilation Design Method for a Highway Twin-Tunnel Based on the Compensation Concept

Table 2

Calculation results for different tunnel design air volume combinations.

Gross power
(m3/s)s1 (m3/s)s2 (m3/s)Δs (m3/s)Δs/s2 (%)s1 (kW)s2 (kW)Δs (kW)Δs/s2 (%)

500476418051551873217.112116.42287.6171.27.48
480457416801752032813.792065.92248.7182.88.13
460438315631912172611.982103.72301.4197.78.59
44041931452206228229.652181.62370.7189.17.98
42040021347217238218.822211.42409.8198.48.23
40038121248227245187.352271.32454.31837.46

Note: when the design air volume of the right tunnel is taken as 400 m3/s, Ln is close to 3800 m; if the ventilation layout is designed according to the data in the table, the pollutant concentration of the second interchange channel in the uphill tunnel would exceed the specified admissible values.