Research Article

Mathematical Analysis of Optimal Operating Conditions in Heating Systems

Table 3

Experimental data.

NumberFrequencyFlow RateSupply Water TemperatureReturn Water TemperatureIndoor TemperaturePump Inlet PressurePump Outlet PressurePower Consumption
Hzm3/h°C°C°CMPaMPakWh

115.020.60667.1365.9018.650.0500.0650.120

215.680.62967.1165.9218.650.0490.0640.128

316.450.67067.0765.9618.650.0480.0650.130

417.500.71067.0465.9918.650.0450.0650.125

518.800.75567.0166.0218.650.0420.0650.130

620.130.81066.9766.0618.650.0400.0650.136

721.300.86666.9566.0818.650.0370.0660.150

823.550.95566.9166.1218.650.0310.0660.168

925.651.04066.8766.1618.650.0260.0680.184

1028.811.17266.8366.2018.650.0160.0700.217

1129.501.19466.8366.2018.650.0150.0700.196

1230.601.23566.8266.2118.650.0110.0690.249

1331.501.27666.8166.2218.650.0080.0700.163

1431.551.28066.8166.2218.650.0080.0700.206

1531.951.29466.8066.2318.650.0060.0690.212

1632.501.32166.8066.2318.650.0050.0710.236

1734.001.37166.7966.2418.650.0000.0700.225