Research Article
Study on the Power-Frequency Waves Distribution Characteristics for Half-Wavelength Transmission Lines Based on the Frequency-Length Factor
Table 1
The information of an UHVAC transmission line.
| Type of wire | 8 × LGJ-500/35 (with 400 mm between conductors in the bundle) |
| Type of the ground wire | JLB20A-170 |
| Information of conductor arrangement | Distance from suspension point of upper conductor to ground: 65 m | Distance from suspension point of lower conductor to ground: 45 m | Vertical distance between suspension points of the ground wire and upper conductor: 12 m | Horizontal distance between upper conductor and central line: 0 | Horizontal distance between lower conductor and central line: 16 | Horizontal distance between ground wire and central line: 14 | Conductor sag: 18.5 m | Ground wire sag: 12.5 m |
| Per unit length parameters | R0 = 0.0081 Ω/km, X0 = 0.2631 Ω/km, C0 = 0.01383 μF/km, Pn = 4063 MW, λ0/2 = 2938 km |
|
|