Study on the Power-Frequency Waves Distribution Characteristics for Half-Wavelength Transmission Lines Based on the Frequency-Length Factor
Table 4
The simulation and calculation results of the voltage and current distribution for asymmetric short circuit.
| ZG (p.u.) | i0.002 | i0.02 | i0.07 | Zf (p.u.) | 0.001 | 0.01 | 0.1 | 0.001 | 0.01 | 0.1 | 0.001 | 0.01 | 0.1 |
| | Simulation | 2925 | 2887 | 2535 | 2850 | 2812 | 2460 | 2649 | 2611 | 2259 | Calculation | 2920 | 2872 | 2528 | 2841 | 2802 | 2455 | 2645 | 2605 | 2253 |
| | Simulation | 1465 | 1427 | 1075 | 1465 | 1427 | 1075 | 1465 | 1427 | 1075 | Calculation | 1465 | 1425 | 1074 | 1465 | 1425 | 1069 | 1465 | 1425 | 1069 |
| | Simulation | 1460 | 1460 | 1460 | 1385 | 1385 | 1385 | 1184 | 1184 | 1184 | Calculation | 1455 | 1453 | 1452 | 1376 | 1373 | 1374 | 1180 | 1176 | 1172 |
|
|