Research Article
Optimal Placement of Wind Power Plants in Transmission Power Networks by Applying an Effectively Proposed Metaheuristic Algorithm
Table 12
The results obtained by five methods for Subcase 2.2.2.
| Method | FBI | HBO | MSGO | CEA | MEA |
| Minimum power loss (MW) | 2.24 | 2.16 | 2.10 | 2.05 | 2.03 | Mean power loss (MW) | 2.61 | 2.37 | 2.46 | 2.27 | 2.31 | Maximum power loss (MW) | 3.93 | 2.64 | 4.24 | 2.70 | 2.77 | STD | 0.28 | 0.13 | 0.37 | 0.15 | 0.14 | N1 | 20 | 60 | 30 | 60 | 60 | N3 | 100 | 100 | 100 | 100 | 100 | Locations of WPPs | 30, 19 | 19, 30 | 30, 19 | 30, 19 | 24, 30 | Generation of WPPs (MW) | 9.83, 9.28 | 9.98, 9.97 | 9.70, 8.15 | 9.99, 9.98 | 9.95, 9.99 | Power factor of WPPs | 0.98, 0.96 | 1.00, 0.96 | 1.00, 0.92 | 0.94, 0.88 | 0.87, 0.99 |
|
|