Research Article

Mathematical Modeling of THD Mitigation Using HAPF for UPS System with Experimental Analysis via Hybrid Interface of Optical USB and Power Quality Meter

Table 2

HAPF control technique result and comparison with past work and standards.

Proposed HAPF control techniqueTHD without HAPF (%)THD with HAPF (%)IEEE STD 519 BS EN61000-3-2:2019 [29]From literature, other works [34]

PQ-Hysteresis (%)46.581.51<5%3.29
DQ-hysteresis46.581.38<5%