Reducing Fault Current by Using FACTS Devices to Improve Electrical Power Flow

Table 1

Effect of FACTS devices in peak fault current for different faults in Bus 6.

Fault typeBus IDWithout FACTS (A in RMS)SSSC (A in RMS)STATCOM (A in RMS)UPFC (A in RMS)

Three-phase faultBus 17210718065186500
Bus 25515551046624540
Bus 34377438640414090
Load A172170160157
Load B237237226224
Load C665675592553

Single line to ground faultBus 16138540553505335
Bus 26202598559706090
Bus 34754459843354396
Load A247245218218
Load B364370346350
Load C236251204212

Double line to ground faultBus 17706759876007595
Bus 26596668165506530
Bus 35258533751805184
Load A181185165153
Load B263269249242
Load C569571506505

Line to line faultBus 17831763272497268
Bus 26982686059806356
Bus 35556542845155178
Load A183180165160
Load B272272251252
Load C562567519515