Research Article
Research into Power Transformer Health Assessment Technology Based on Uncertainty of Information and Deep Architecture Design
Table 5
Grade membership of typical transformer defect.
| Defect type | Normal | Attention | Abnormal | Serious | Condition |
| Interturn short circuit of winding | 0.5590 | 0.0000 | 0.1487 | 0.2923 | Normal | Iron core multipoint grounding | 0.1196 | 0.0011 | 0.0002 | 0.8791 | Serious | Arc discharge | 0.6328 | 0.0002 | 0.0817 | 0.2853 | Normal | Current circuit overheating | 0.6702 | 0.0012 | 0.1207 | 0.2079 | Normal | Winding deformation | 0.6045 | 0.2112 | 0.0910 | 0.0933 | Normal | Partial discharge | 0.7497 | 0.0017 | 0.0001 | 0.2485 | Normal | Aging of oil paper insulation | 0.5925 | 0.1402 | 0.2673 | 0.0000 | Normal | Wetted insulation | 0.2699 | 0.5039 | 0.0297 | 0.1965 | Attention |
|
|